Danfoss AK-SM 800A Series Path Traversal Vulnerability
TL;DR 📌
- Danfoss AK-SM 800A Series contains a path traversal vulnerability that could allow an attacker to access and read underlying server system files via the XML interface.
- Highest CVSS: 8.8 (High).
- Listed in CISA KEV (2026-11-25) — this is being exploited in the wild.
- Check the advisory for fixed releases — remediation detail is in the vendor link below.
- CVEs: CVE-2023-25914.
What it is
CVE-2023-25914 is a path traversal vulnerability in the Danfoss AK-SM 800A Series, reachable through the device’s XML interface. An attacker with low-privilege authenticated access can use crafted requests to escape the intended directory and read arbitrary files on the underlying server’s filesystem.
The access path requires authentication but no user interaction, and the attack is carried out over the network (CVSS vector AV:N/AC:L/PR:L/UI:N). Because the flaw sits in a server-side interface rather than requiring local access, any authenticated network client that can reach the XML interface is a potential attack path.
Danfoss and NVD describe the impact as full system compromise: the files exposed through this traversal can include data sufficient to escalate beyond simple file disclosure. The CVSS score of 8.8 (High) reflects high impact across confidentiality, integrity and availability, consistent with an attacker using leaked system files to pivot further into the device or its environment.
This CVE is listed in the CISA Known Exploited Vulnerabilities catalogue, added on 2026-11-25, so it is known to be exploited.
What to do
- Identify all AK-SM 800A Series units on your network. The last vulnerable version confirmed is 3.3; no fixed version is listed in the advisory at this time, so consult Danfoss directly for a patched release before assuming the device is covered.
- Restrict network access to the AK-SM 800A’s XML interface to trusted management hosts only — do not expose it to general network segments or the internet.
- Review and tighten authentication credentials for any accounts with access to the device, since exploitation requires only low-privilege authenticated access.
- Given its presence in the CISA KEV catalogue, treat this as a priority for remediation and apply CISA’s required actions and timelines if you are a federal agency, or align with equivalent internal patching priorities otherwise.
- Monitor logs for unusual file-read patterns or traversal-style requests (e.g. “../” sequences) against the XML interface as a stopgap while awaiting vendor guidance on a fix.
For leadership 🧭
Executive summary. An authenticated attacker on these Danfoss refrigeration controllers can pull system files through the XML interface, potentially gaining enough information to take over the device entirely. It is listed in CISA’s Known Exploited Vulnerabilities catalogue, so treat it as an active, time-critical risk rather than a theoretical one.
Why it matters:
- The XML interface on AK-SM 800A units accepts crafted requests from any authenticated network client, not just local operators, widening the pool of potential attackers to anyone with valid low-level credentials and network reach.
- Danfoss and NVD both state the exposed files can be sufficient for full system compromise, meaning this is not limited to simple file disclosure but can be a stepping stone to control of the controller.
- No fixed version is listed against the last known vulnerable build (3.3), so sites cannot assume an update alone resolves exposure without checking directly with Danfoss.
- Confirmed inclusion in CISA’s KEV catalogue means this flaw is known to be exploited, raising the urgency for sites running these controllers in refrigeration or building management environments.
Now / Next / Later:
- Now: Identify every AK-SM 800A Series unit reachable on your network and immediately restrict access to its XML interface to a small set of trusted management hosts.
- Next: Contact Danfoss directly to confirm whether a patched release now exists beyond version 3.3, and schedule an update or compensating network segmentation in your next change window.
- Later: Establish a standing inventory and access-control process for building/refrigeration management devices like the AK-SM 800A, so interfaces such as this are never reachable from general network segments and credential hygiene is reviewed on a regular cycle.