Danfoss AK-SM 800A Series Improper Input Validation Vulnerability
TL;DR 📌
- Danfoss AK-SM 800A Series contains an improper input validation vulnerability that could allow a remote attacker to run arbitrary commands on the affected system.
- Highest CVSS: 9.9 (Critical).
- Listed in CISA KEV (2026-11-25) — this is being exploited in the wild.
- Check the advisory for fixed releases — remediation detail is in the vendor link below.
- CVEs: CVE-2023-25915.
What it is
CVE-2023-25915 affects the Danfoss AK-SM 800A Series, a refrigeration and HVAC controller platform. The flaw is an improper input validation issue that allows an authenticated remote attacker to execute arbitrary commands on the device.
The CVSS vector (AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H) shows this is reachable over the network with low attack complexity and no user interaction, but it does require the attacker to hold some level of credentials on the target (PR:L). Once that bar is cleared, the scope change (S:C) combined with full confidentiality, integrity and availability impact indicates that command execution on the controller can affect resources beyond the vulnerable component itself.
Danfoss lists version 3.3 as the last known vulnerable release. The advisory does not specify a fixed version, so anyone running this platform should check directly with Danfoss for the patched release applicable to their deployment.
This CVE is listed in the CISA Known Exploited Vulnerabilities catalogue (added 25 November 2026), meaning it is known to be exploited.
What to do
- Treat this as a priority patching item given its KEV listing and 9.9 CVSS score — confirm with Danfoss whether a fixed build beyond 3.3 is available for your AK-SM 800A deployment, as none is specified in the public advisory.
- Review who holds credentials on AK-SM 800A units. Since exploitation requires low-privilege authenticated access, tightening account provisioning and removing unused or shared accounts reduces the pool of attackers who can reach the vulnerable function.
- Restrict network reachability to the AK-SM 800A management interface — place it behind a firewall or VPN so it is not exposed to general network or internet access, given the AV:N network vector.
- Check logs on affected controllers for command execution activity inconsistent with normal operation, particularly from authenticated sessions.
- Track Danfoss’s advisory page for CVE-2023-25915 for the fixed release once published, and apply it as soon as it’s available given the KEV listing.
For leadership 🧭
Executive summary. Danfoss AK-SM 800A refrigeration and HVAC controllers have a critical, actively exploited flaw that lets anyone with low-level login credentials take full control of the device over the network. Danfoss has not published a fixed version, so immediate action is to cut off network exposure and tighten who holds credentials, not wait for a patch.
Why it matters:
- Exploitation needs only low-privilege authenticated access (PR:L), so any shared, default, or loosely provisioned account on the AK-SM 800A is a usable foothold for arbitrary command execution.
- The scope change (S:C) combined with full confidentiality, integrity and availability impact means a compromised controller can affect systems beyond itself, not just the unit being attacked.
- CVE-2023-25915 is in the CISA KEV catalogue, confirming it is being exploited, yet Danfoss has not published a fixed version beyond the last known vulnerable release 3.3.
- These controllers manage refrigeration and HVAC, so command execution translates directly into physical process disruption, not just a data breach.
Now / Next / Later:
- Now: Identify every AK-SM 800A unit on your network and confirm whether its management interface is reachable from general network or internet access; if so, put it behind a firewall or VPN immediately.
- Next: Audit and prune all accounts with credentials on AK-SM 800A units, removing shared, default, or unused logins, since the attack requires only low-privilege authenticated access.