Danfoss AK-SM 800A Series Improper Authentication Vulnerability

🚨SEVERITY: HIGH — CVSS 8.2Security Advisory

TL;DR 📌

  • Danfoss AK-SM 800A Series contains an improper authentication vulnerability that could allow an attacker to generate a web report exposing sensitive information, including internal IP addresses, usernames, and store names.
  • Highest CVSS: 8.2 (High).
  • Listed in CISA KEV (2026-11-25) — this is being exploited in the wild.
  • Fixed in 4.2 — upgrade to this release or later.
  • CVEs: CVE-2025-41450.

What it is

CVE-2025-41450 is an improper authentication flaw in the Danfoss AK-SM 800A Series, affecting versions prior to 4.2. It allows an attacker to generate a web report that exposes sensitive information, including internal IP addresses, usernames, and store names.

The CVSS vector (AV:N/AC:H/PR:N/UI:R/S:C) indicates the vulnerability is reachable over the network without requiring valid credentials, though exploitation has high attack complexity and requires user interaction. The scope change (S:C) means the impact extends beyond the vulnerable component itself.

This CVE is listed in the CISA Known Exploited Vulnerabilities catalogue, added on 2026-11-25, so it is known to be exploited.

What to do

  • Upgrade AK-SM 8xxA Series units to version 4.2 or later, which addresses this vulnerability.
  • Treat any instance running a version prior to 4.2 as exposed; prioritise units reachable from untrusted networks.
  • Since the flaw involves improper authentication on web reporting functionality, review who can reach the device’s web interface and restrict network access where upgrades cannot be applied immediately.
  • Given the CISA KEV listing, apply the fix on an expedited timeline rather than waiting for a routine maintenance window.
  • Consult the Danfoss advisory for deployment-specific guidance, as no detailed remediation steps beyond the fixed version are available here.

For leadership 🧭

Executive summary. Refrigeration controllers running AK-SM 800A software before version 4.2 can be tricked into producing a report that discloses internal network details, account names and store identifiers to an unauthenticated requester. Given this is listed in CISA’s Known Exploited Vulnerabilities catalogue, upgrading or isolating affected units should happen now, not at the next maintenance cycle.

Why it matters:

  • The AK-SM 800A is a refrigeration monitoring and control unit, so the leaked internal IPs and usernames give an attacker a map of the site network and account names to target next.
  • No credentials are required to trigger the web report generation, only network reachability and some user interaction, meaning exposure depends on who can send requests to the device’s web interface.
  • Store names appearing in the disclosed data make it straightforward to tie a compromised controller to a specific retail or commercial site.
  • The scope change in the CVSS vector means the impact is not confined to the controller itself but spills into the wider environment it reports on.

Now / Next / Later:

  • Now: Identify every AK-SM 8xxA unit on the network, note its firmware version, and restrict network access to any reachable from untrusted networks until confirmed patched.
  • Next: Upgrade all affected AK-SM 800A Series controllers to version 4.2 or later during the next available change window, prioritising internet- or remotely-reachable units first.
  • Later: Establish network segmentation for refrigeration and building-control devices so their web interfaces are never directly reachable without authentication at the network boundary, and track firmware versions as part of routine OT asset inventory.

Source